We can easily normally satisfy our respected buyers with our excellent high-quality, excellent selling price and good service due to we've been far more expert and more hard-working and do it in cost-effective way for Fire Protection Sprinkler, Pendent Fire Sprinkler, Sprinkler System Fire, Our final target is To consider the most effective, To be the Best. Please experience cost-free to call with us if you have any prerequisites.
High Quality 3mm 141℃ Bulb - 3mm Fast response sprinkler bulbs – Zhurong Detail:

kjhgoiuhjkl

Size(mm) Temperature Rating (℃/°F) Color
A 2.4 68℃ / 155°F red
B 1.5 79℃ / 175°F yellow
C <4.2 93℃ / 200°F green
D 3±0.1 141℃ / 286°F blue
d1 3.5±0.4
d2 3.5±0.3
L 23±0.5
l1 20±0.4
l2 19.8±0.4
Glass bulb load(N) Average Cursh load(X) 3600
lower Tolerance Limit(TL) ≥1600
aximum clamping torque 6.5 N·cm
Response time index(m*s)0.5 RTI≤50

 

The printed text on 3mm sprinkler bulb is “ZJCY”. Compared with 5mm sprinkler bulb, its response will be faster, RTI ≤ 50, where RTI is a coefficient measured under standard conditions to measure the sensitivity of sprinkler bulb. Expressions:RTI= τ u ½

Where: RTI – response time coefficient, unit (m * s) ½;
τ- Response time constant, in s;
u – gas flow rate, unit: m / s
The quality of the sprinkler bulb fully complies with the Chinese national standard GB18428-2010. The diameter of the sprinkler bulb is 3mm, and the deviation from the nominal diameter will not exceed ± 0.1mm; Its length is 23mm and the deviation from the nominal length will not exceed 0.5mm.
The average crushing load of the sprinkler bulb is 3600n. During the test, the sprinkler bulb will be fixed between the supporting elements in an appropriate way, and the supporting elements are made of steel. The Rockwell hardness is (44 ± 6) HRC, which meets the corresponding service requirements. Then, apply a uniform load along the axis of the sprinkler bulb until the sprinkler bulb bursts, and the rate of load increase is (250 ± 25) N / s. The maximum deviation of the equipment used to measure the crushing load shall not exceed ± 1% of the measured value. Use multiple groups of measured data to calculate the average value and standard deviation of the crushing load and judge whether the results meet the specified standards.


Product detail pictures:

High Quality 3mm 141℃ Bulb - 3mm Fast response sprinkler bulbs – Zhurong detail pictures

High Quality 3mm 141℃ Bulb - 3mm Fast response sprinkler bulbs – Zhurong detail pictures

High Quality 3mm 141℃ Bulb - 3mm Fast response sprinkler bulbs – Zhurong detail pictures

High Quality 3mm 141℃ Bulb - 3mm Fast response sprinkler bulbs – Zhurong detail pictures

High Quality 3mm 141℃ Bulb - 3mm Fast response sprinkler bulbs – Zhurong detail pictures

High Quality 3mm 141℃ Bulb - 3mm Fast response sprinkler bulbs – Zhurong detail pictures


Related Product Guide:

carry on to boost, to guarantee products excellent in line with market and consumer standard specifications. Our enterprise has a quality assurance system are actually established for High Quality 3mm 141℃ Bulb - 3mm Fast response sprinkler bulbs – Zhurong , The product will supply to all over the world, such as: Turkey, Belgium, Riyadh, Customer satisfaction is our first goal. Our mission is to pursue the superlative quality, making continual progress. We sincerely welcome you to make progress hand in hand with us, and construct a prosperous future together.
  • We are long-term partners, there is no disappointment every time, we hope to maintain this friendship later!
    5 Stars By Laurel from Slovakia - 2018.04.25 16:46
    In general, we are satisfied with all aspects, cheap, high-quality, fast delivery and good procuct style, we will have follow-up cooperation!
    5 Stars By Janice from Riyadh - 2017.12.02 14:11
    Write your message here and send it to us