New Arrival China Early Suppression - Fusible alloy/Sprinkler bulb ESFR sprinkler heads – Zhurong
New Arrival China Early Suppression - Fusible alloy/Sprinkler bulb ESFR sprinkler heads – Zhurong Detail:
Model | ESFR-202/68℃ P | ESFR-202/68℃ U | ESFR-202/74℃ P | ESFR-202/74℃ U | ESFR-242/74℃ P | ESFR-242/74℃ U | ESFR-323/74℃ P | ESFR-323/74℃ U | ESFR-363/74℃ P | ESFR-363/74℃ U |
Mounting | Pendent | Upright | Pendent | Upright | Pendent | Upright | Pendent | Upright | Pendent | Upright |
Flow Characteristics | 202 | 202 | 242 | 323 | 363 | |||||
Thread Size | R₂ 3/4 | R₂ 1 | ||||||||
Nominal action temperature | 68℃ | 74℃ | ||||||||
Nominal Working Pressure | 1.2MPa | |||||||||
Factory test pressure | 3.4MPa |
Background – History
In the 1980s, early suppression, fast response (ESFR) sprinkler systems were developed as an alternative to in-rack systems. They were designed to actually suppress or extinguish the fire, while conventional sprinklers can only control fires, therefore eliminating the need for extinguishment by firefighters.
How do they work? ESFR sprinklers are designed to release 2-3 times the amount of water of conventional sprinkler heads and to emit larger droplets of water, which in turn have a greater momentum than droplets emitted from conventional heads. As a result, more water and a greater share of the water reaches the fire allowing the flames to be extinguished.
Application
In general, ESFR systems can be used in warehouses with storage that do not exceed 40 feet in overall height, and with a ceiling height of less than 45 feet. And there are sprinkler system protection schemes that will allow storage above those heights. These may include in-rack sprinklers or a combination of ESFR with in-rack sprinklers.
ESFR systems are designed to protect a wide array of commodities. This provides more flexibility in warehouse operations when compared to control mode (conventional) sprinkler systems, which are designed to protect only the commodities that were stored at the time of system installation. If the storage situation requires in-rack sprinklers to be installed to the existing control mode systems of a warehouse building, often building owners prefer to change over to ESFR, simply because then there is no need to worry about damaging in-rack sprinkler heads during normal storage operations. Additionally, in-rack sprinklers have to be removed and sometimes replaced with each new tenant, since the tenants own the racks. Therefore, converting to an ESFR system is at times more cost-effective in the long run.
Product detail pictures:






Related Product Guide:
We generally continually give you quite possibly the most conscientious shopper company, and the widest variety of designs and styles with finest materials. These endeavours include the availability of customized designs with speed and dispatch for New Arrival China Early Suppression - Fusible alloy/Sprinkler bulb ESFR sprinkler heads – Zhurong , The product will supply to all over the world, such as: Pakistan, Albania, Bogota, With a fully integrated operation system, our company has won a good fame for our high quality products, reasonable prices and good services. Meanwhile, we have established a strict quality management system conducted in material incoming, processing and delivery. Abiding by the principle of Credit first and customer supremacy, we sincerely welcome clients from home and abroad to cooperate with us and advance together to create a brilliant future.

The supplier cooperation attitude is very good, encountered various problems, always willing to cooperate with us, to us as the real God.
