We offer fantastic energy in high quality and enhancement,merchandising,profits and promoting and procedure for Two-Piece Flush Escutcheon, Zstx80-93℃, Upright Type Safety Fire Fighting Sprinkler, We are willing to give you the best suggestions on the designs of your orders in a professional way if you need. In the meantime, we keep on developing new technologies and creating new designs so as to make you ahead in the line of this business.
Short Lead Time for Glass Bulb 68 Degree Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong Detail:

Size(mm) Temperature Rating (℃/°F) Color
A 2.4 68℃ / 155°F red
B 1.5 79℃ / 175°F yellow
C <4.2 93℃ / 200°F green
D 3±0.1 141℃ / 286°F blue
d1 3.5±0.4
d2 3.5±0.3
L 23±0.5
l1 20±0.4
l2 19.8±0.4
Glass bulb load(N) Average Cursh load(X) 3600
lower Tolerance Limit(TL) ≥1600
aximum clamping torque 6.5 N·cm
Response time index(m*s)0.5 RTI≤50

kjhgoiuhjkl

The printed text on 3mm sprinkler bulb is “ZJCY”. Compared with 5mm sprinkler bulb, its response will be faster, RTI ≤ 50, where RTI is a coefficient measured under standard conditions to measure the sensitivity of sprinkler bulb. Expressions:RTI= τ u ½

Where: RTI – response time coefficient, unit (m * s) ½;
τ- Response time constant, in S;
u – gas flow rate, unit: M / s
The quality of the sprinkler bulb fully complies with the Chinese national standard GB18428-2010. The diameter of the sprinkler bulb is 3mm, and the deviation from the nominal diameter will not exceed ± 0.1mm; Its length is 23mm and the deviation from the nominal length will not exceed 0.5mm.
The average crushing load of the sprinkler bulb is 3600n. During the test, the sprinkler bulb will be fixed between the supporting elements in an appropriate way, and the supporting elements are made of steel. The Rockwell hardness is (44 ± 6) HRC, which meets the corresponding service requirements. Then, apply a uniform load along the axis of the sprinkler bulb until the sprinkler bulb bursts, and the rate of load increase is (250 ± 25) n / s. The maximum deviation of the equipment used to measure the crushing load shall not exceed ± 1% of the measured value. Use multiple groups of measured data to calculate the average value and standard deviation of the crushing load and judge whether the results meet the specified standards.


Product detail pictures:

Short Lead Time for Glass Bulb 68 Degree Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong detail pictures

Short Lead Time for Glass Bulb 68 Degree Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong detail pictures

Short Lead Time for Glass Bulb 68 Degree Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong detail pictures

Short Lead Time for Glass Bulb 68 Degree Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong detail pictures


Related Product Guide:

All we do is usually affiliated with our tenet Buyer to start with, Belief to start with, devoting about the food packaging and environmental defense for Short Lead Time for Glass Bulb 68 Degree Fire Sprinkler - 3mm Fast response sprinkler bulbs – Zhurong , The product will supply to all over the world, such as: Latvia, Swansea, Philadelphia, With the spirit of credit first, development through innovation, sincere cooperation and joint growth, our company is striving to create a brilliant future with you, so as to become a most valuable platform for exporting our goods in China!
  • High Quality, High Efficiency, Creative and Integrity, worth having long-term cooperation! Looking forward to the future cooperation!
    5 Stars By Letitia from Holland - 2017.09.16 13:44
    Production management mechanism is completed, quality is guaranteed, high credibility and service let the cooperation is easy, perfect!
    5 Stars By Isabel from Slovenia - 2017.01.28 19:59
    Write your message here and send it to us