The key to our success is Good Products Good quality, Reasonable Value and Efficient Service for 150 Gm Sprinkler Head, Rapid Response Fire Sprinkler, Cantilever Standard Response Fire Sprinklers, As a result of our hard perform, we have always been around the forefront of clean technology merchandise innovation. We've been a eco-friendly partner you can rely on. Get hold of us today for additional data!
Top Suppliers Glass Sprinkler Bulbs - sprinkler bulbs customized ( length, logo, temperature ) – Zhurong Detail:

Size(mm) Temperature Rating(℃/°F) Color
A 3.8 57℃ / 135°F orange
B 2.02 68℃ / 155°F red
C <4.5 79℃ / 175°F yellow
D 5±0.1 93℃ / 200°F green
d1 5.3±0.2 141℃ / 286°F blue
d2 5.3±0.3
L 24.5±0.5
l1 20±0.4
l2 19.8±0.4
Glass bulb load(N) Average Cursh load(X) 4000
lower Tolerance Limit(TL) ≥2000
Maximum clamping torque 8.0 N·cm
Response time index(m*s)0.5 80<RTI≤350

jgf

As a professional sprinkler bulb manufacturer, MH has its own special R &amp; D team, which is committed to continuously improving the quality and characteristics of products and meeting the needs of various customers, including all the requirements for sprinkler bulbs in GB 16809-2008 for fire windows and GB / T 25205-2010 for shower heads.
Our sprinkler bulb can be applied to almost any place where temperature sensing sprinkler bulb release mechanism is needed, such as kitchen smoke hood, paint spraying room, fire damper, smoke exhaust fan, etc. In order to meet the different needs of our customers for sprinkler bulb size, specification and RTI, we have specially set up a standby assembly line and separate machine production. All products support OEM / ODM.

All sprinkler bulbs will be inspected when leaving the factory, including:

1. Appearance and size
Ensure that the outer surface of all sprinkler bulbs is not damaged, there are no bubbles or other impurities inside the glass material, and the bubble size in the working liquid of sprinkler bulbs of the same specification is uniform. The dimensional deviation of all sprinkler bulbs is within the specified allowable range. The temperature and color of all sprinkler bulbs are easy to identify.
2. Static operating temperature
The static operating temperature of all sprinkler bulbs shall not exceed the following temperature range: X ± (0.035x + 0.62) x refers to the nominal operating temperature, and the unit is Celsius (℃)
3. Crushing load
The average crushing load shall not be lower than the specified value, and the lower limit of crushing load error shall not be lower than 50% of the average crushing load.

 


Product detail pictures:

Top Suppliers Glass Sprinkler Bulbs - sprinkler bulbs customized ( length, logo, temperature ) – Zhurong detail pictures

Top Suppliers Glass Sprinkler Bulbs - sprinkler bulbs customized ( length, logo, temperature ) – Zhurong detail pictures

Top Suppliers Glass Sprinkler Bulbs - sprinkler bulbs customized ( length, logo, temperature ) – Zhurong detail pictures

Top Suppliers Glass Sprinkler Bulbs - sprinkler bulbs customized ( length, logo, temperature ) – Zhurong detail pictures

Top Suppliers Glass Sprinkler Bulbs - sprinkler bulbs customized ( length, logo, temperature ) – Zhurong detail pictures


Related Product Guide:

We emphasize progress and introduce new solutions into the market each year for Top Suppliers Glass Sprinkler Bulbs - sprinkler bulbs customized ( length, logo, temperature ) – Zhurong , The product will supply to all over the world, such as: Luxembourg, Sweden, Portugal, Being the top solutions of our factory, our solutions series have been tested and won us experienced authority certifications. For additional parameters and item list details, be sure to click the button to acquire additional nformation.
  • Hope that the company could stick to the enterprise spirit of Quality, Efficiency, Innovation and Integrity, it will be better and better in the future.
    5 Stars By Eartha from Malaysia - 2018.10.09 19:07
    Managers are visionary, they have the idea of mutual benefits, continuous improvement and innovation, we have a pleasant conversation and Cooperation.
    5 Stars By Jill from Germany - 2018.05.13 17:00
    Write your message here and send it to us